Model Item
|
PM-4000GT
|
Inverter Technology
|
Conversion Mode
|
Sine-wave, Current source, High frequency PWM
|
Isolation Method
|
Transformer-less Design *
|
DC Input Data
|
|
Nominal DC Voltage
|
360 VDC
|
Max. DC input Voltage
|
500 VDC
|
Working range
|
120VDC~500VDC **
|
Max DC input current (Each MPPT Tracker)
|
14 Amp
|
MPPT Range
|
150 VDC ~ 450 VDC
|
MPPT Tracker
|
2
|
AC Output Data
|
|
Nominal AC Power
|
4000
|
Max. AC Power
|
4200
|
Nominal AC Voltage
|
AC 230V
|
Output Connect Method
|
1-Phase / 2-Wires(L, N, G) or 1-Phase / 3-Wires(L1, L2, G)
|
AC Voltage Rang
|
184~264.5Vac(Base on 230 Vac)
|
Nominal AC Current
|
17.4Amp
|
Frequency
|
50/60Hz Auto-Selection (47.5 ~ 50.2 Hz or 59.3 ~ 60.5 Hz)
|
Power Factor
|
>0.99 with nominal AC current
|
Current Distortion
|
Total Harmonic current : Less than 5% Single Harmonic current : Less than 3%
|
Efficiency Data
|
|
Max. efficiency
|
>96%
|
Euro efficiency
|
>94%
|
CEC efficiency
|
>94%
|
Environmental
|
|
Operating Temperature
|
-25 °C ~ + 50 °C
|
-13 °F ~ 122 °F
|
Humidity
|
0 to 90%(Without condensation)
|
Altitude
|
0 ~ 2000 M / 0 ~ 6600 ft
|
Mechanical
|
|
Dimensions (H x W x D in mm )
|
455 x 510 x 170
|
Weight (Kgs / Lbs)
|
28 / 62
|
Protection Class
|
IP65, outdoor
|
Cooling
|
Free Convection
|
AC Connector
|
Terminal
|
DC Connector
|
Multi-Contact
|
Communication
|
|
Communication Interface
|
RS232
|
USB, RS485, Dry contact, TCP/IP
|
Front Panel
|
|
LCD
|
Boost input Voltage/Boost input Current/Boost input Power/AC output Voltage /AC output frequency/AC output current /AC output power/AC Energy yield/Inner Temperature/Heat sink Temperature /Status message/ Error message
|
LED
|
Leakage current fault or DC input isolation fault
|
Spec. of Utility is not matches with the Utility specifications of the inverter
|
Solar Cell power is greater or smaller than sleep power
|
Key Pad
|
UP key/ Down key/ Function key/ Enter key
|
Protection
|
|
Utility
|
Over/under Voltage, Over/under Frequency, Ground fault, DC Isolation fault
|
Islanding operation detection
|
Passive : Voltage phase jump detection Active : Reactive power control
|
Over Temperature
|
reduced output power
|
Certification
|
|
Safety
|
VDE 0126-1-1, EN50178, IEC62103
|
UL1741, IEEE1547
|
EMI/EMC
|
EN 6 1000-6-1, EN 6 1000-6-2, EN 6 1000-6-3, EN 6 1000-6-4
|