Model No. |
PM-2400LC-24
|
Output Power Continuous |
2400W
|
Max. Surge Power |
4800W
|
1. Input Section |
Input Nominal Voltage |
110Vac or 220Vac
|
Input Voltage Range |
60V~140Vac or 120V~280Vac
|
Line Low Transfer |
60Vac ± 2% or 120Vac ± 2%
|
Line Low Return |
65Vac ± 2% or 130Vac ± 2%
|
Line High Transfer |
140Vac ¡Ó 2% or 280Vac ¡Ó 2%
|
Line High Return |
130Vac ± 2% or 260Vac ± 2%
|
Input Frequency |
50Hz / 60Hz (45Hz~70Hz)
|
2. Output Section |
Output Voltage |
100 / 110 / 115 / 120Vac or 200 / 220 / 230 / 240Vac re-settable via LCD panel
|
Waveform |
Pure Sine Wave
|
Voltage Regulation (Batt. Mode) |
< 3% RMS for entire battery voltage range
|
Output Frequency |
50Hz or 60Hz ± 0.1Hz
|
Efficiency |
> 80%
|
Maximum Load |
Up to short circuit
|
Asymmetrical Load Max. |
Up to nominal output power
|
Overload and Short Circuit Protection |
Automatic disconnection
|
Overheating Temperature Protection |
Acoustic warning before shut-off. Automatic restart
|
Power Factor |
0.8
|
3. Battery Section |
Voltage Range |
24VDC (20~32VDC)
|
Backup Time (at full load) |
Long time available
|
Input Frequency Range |
45~70Hz
|
Max. Charging Current (3 steps selectable) |
60/80/100Amp
|
4. Display |
LCD Display |
UPS status, I/P&O/P Voltage Frequency, Load%, Battery Voltage & %, Temperature, Model
|
LED Display |
Normal (Green), Warning (Yellow), Fault (Red)
|
5. Audible Alarm |
Battery Mode |
Beeping every 4 seconds
|
Low Battery |
Beeping every second
|
Overload |
Beeping twice per second
|
Temperature Compensation (Option) |
3mV / °C cell
|
6. General date |
AC By Pass Time (UPS Mode) |
< 8 ms.
|
Operation Temperature |
-20 °C to +55 °C
|
Audible Noise |
Less than 55dBA (at 1M)
|
Relative Humidity |
0-95% non-condensing
|
Dimensions (L x W x H mm) |
450 × 298 × 190
|
Weight (by Kg/s) |
23.0
|